Abstract
The problem of avoiding sustained oscillations in power systems with dynamic loads and tap changing transformers is analyzed. Deadband size adjustment is used to eliminate limit cycles which originate from tap-load interactions. The analysis demonstrates the role of load dynamics in providing a deadband setting which guarantees the absence of sustained oscillatory behavior.